Moxa NPort S9450I-2M-ST-HV-T
NPort S9450I-2M-ST-HV-T
NPort S9450I Series
4-port RS-232/422/485 rugged device server, 3 10/100M Ethernet ports, 2 100M multi-mode fiber ports with ST connectors, 88-300 VDC or 85-264 VAC, -40 to 85°C operating temperature
Input/Output Interface
Alarm Contact Channels
- 2, Resistive load: 1 A @ 24 VDC
Digital Input Channels
- 2
Digital Inputs
- +13 to +30 V for state 1
-30 to +1 V for state 0
Max. input current: 8 mA
- +13 to +30 V for state 1
Ethernet Interface
10/100BaseT(X) Ports (RJ45 connector)
- 3
100BaseFX Ports (multi-mode ST connector)
- 2
Magnetic Isolation Protection
- 1.5 kV (built-in)
Optical Fiber
Optical Fiber
100BaseFX Multi-Mode Single-Mode Fiber Cable Type OM1 50/125 µm G.652 800 MHz x km Typical Distance 4 km 5 km 40 km Wavelength Typical (nm) 1300 1310 TX Range (nm) 1260 to 1360 1280 to 1340 RX Range (nm) 1100 to 1600 1100 to 1600 Optical Power TX Range (dBm) -10 to -20 0 to -5 RX Range (dBm) -3 to -32 -3 to -34 Link Budget (dB) 12 29 Dispersion Penalty (dB) 3 1 Note: When connecting a single-mode fiber transceiver, we recommend using an attenuator to prevent damage caused by excessive optical power.
Note: Compute the ?typical distance? of a specific fiber transceiver as follows: Link budget (dB) > dispersion penalty (dB) + total link loss (dB).
Standards
- IEEE 802.1D-2004 for Spanning Tree Protocol
IEEE 802.1p for Class of Service
IEEE 802.1Q for VLAN Tagging
IEEE 802.1w for Rapid Spanning Tree Protocol
IEEE 802.1X for authentication
IEEE 802.3 for 10BaseT
IEEE 802.3ad for Port Trunk with LACP
IEEE 802.3u for 100BaseT(X) and 100BaseFX
- IEEE 802.1D-2004 for Spanning Tree Protocol
Switch Properties
IGMP Groups
- 256
Max. No. of VLANs
- 64
Priority Queues
- 4
VLAN ID Range
- VID 1 to 4094
Ethernet Software Features
Configuration Options
- Command Line Interface (CLI) through Serial/Telnet/SSH, Web Console (HTTP/HTTPS), Windows Utility
Management
- DHCP Client, DHCP Option 82, HTTP, IEC 61850 MMS, IPv4, LLDP, Port Mirror, RARP, RMON, SMTP, SNMPv1/v2c/v3, Syslog, Telnet, TFTP, Web Console
Filter
- GMRP, GVRP, IGMP v1/v2
Windows Real COM Drivers
- Windows 95/98/ME/NT/2000, Windows XP/2003/Vista/2008/7/8/8.1/10 (x86/x64), Windows 2008 R2/2012/2012 R2 (x64), Windows Embedded CE 5.0/6.0, Windows XP Embedded
Linux Real TTY Drivers
- Kernel versions: 2.4.x, 2.6.x, 3.x, 4.x, and 5.x
Fixed TTY Drivers
- SCO UNIX, SCO OpenServer, UnixWare 7, QNX 4.25, QNX 6, Solaris 10, FreeBSD, AIX 5.x, HP-UX 11i, Mac OS X
Android API
- Android 3.1.x and later
Industrial Protocols
- Modbus TCP Server (Slave), DNP3 TCP Outstation
Time Management
- NTP Server/Client, SNTP
MIB
- Bridge MIB, Device Settings MIB, Ethernet-like MIB, MIB-II, P-BRIDGE MIB, Q-BRIDGE MIB, RFC1213, RFC1317, RMON MIB Groups 1, 2, 3, 9, RSTP MIB
Redundancy Protocols
- RSTP, Turbo Chain, Turbo Ring v1, Turbo Ring v2
Security
- HTTPS/SSL, Local Account Accessibility, TACACS+, RADIUS, SSH
Serial Interface
Connector
- DB9 male
No. of Ports
- 4
Serial Standards
- RS-232, RS-422, RS-485
Operation Modes
- Real COM mode, RFC2217 mode, TCP Client mode, TCP Server mode, UDP mode, Modbus mode, DNP3 mode, DNP3 Raw Socket mode, Disabled
Baudrate
- 50 bps to 921.6 kbps (supports non-standard baudrates)
Data Bits
- 5, 6, 7, 8
Stop Bits
- 1, 1.5, 2
Parity
- None, Even, Odd, Space, Mark
Flow Control
- None, RTS/CTS, XON/XOFF
Isolation
- 2 kV
Surge
- 4 kV
RS-485 Data Direction Control
- ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485
- 1 kilo-ohm, 150 kilo-ohms
Terminator for RS-485
- 120 ohms
Console Port
- RS-232 (TxD, RxD, GND), 10-pin RJ45 (19200, n, 8, 1)
Serial Signals
RS-232
- TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422
- Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w
- Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w
- Data+, Data-, GND
DIP Switch Configuration
Ethernet Interface
- Turbo Ring, Master, Coupler, Reserved
Modbus TCP
Max. No. of Client Connections
- 32
Max. No. of Server Connections
- 16
DNP3 (Transparent)
Max. No. of Master Connections
- 16
Max. No. of Outstation Connections
- 32
Power Parameters
No. of Power Inputs
- 2
Power Connector
- 1 removable 5-contact terminal block(s)
Reverse Polarity Protection
- Supported
Input Current
- 80 mA @ 110 VDC
Input Voltage
- 110/220 VAC/VDC (85 to 264 VAC, 88 to 300 VDC)
Physical Characteristics
Housing
- Metal
Dimensions
- 80 x 160 x 109 mm (3.15 x 6.30 x 4.29 in)
Weight
- Product only: 2.54 kg (5.60 lb)
Installation
- DIN-rail mounting, Wall mounting (with optional kit)
Environmental Limits
Operating Temperature
- -40 to 85°C (-40 to 185°F)
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
- 5 to 95% (non-condensing)
Standards and Certifications
EMC
- EN 61000-6-2/-6-4
EMI
- CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV
IEC 61000-4-5 Surge: Power: 6 kV; Signal: 4 kV
IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
IEC 61000-4-8 PFMF
IEC 61000-4-11 DIPs
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
Environmental Testing
- IEC 60068-2-2
IEC 60068-2-14
- IEC 60068-2-2
Power Substation
- IEC 61850-3, IEEE 1613
Hazardous Locations
- UL/cUL Class I Division 2 Groups A/B/C/D
Safety
- EN 61010-2-201, UL 61010-2-201
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6, IEC 60068-2-64
Declaration
Green Product
- RoHS, CRoHS, WEEE
MTBF
Time
- 347,436 hrs
Standards
- Telcordia SR332
Warranty
Warranty Period
- 5 years
Details